Equation 7 · Part 2 · The Physical Plant: Power, Cooling, and Networks in an AI Datacenter

Symbol c_p

ρcp≈1.17 kJ/(m3⋅K)\rho c_p \approx 1.17\ \mathrm{kJ/(m^3{\cdot}K)}
cpc_p

What this part means

the specific heat capacity.

Its job in the formula

cpc_p is a part of this expression. Its role is fixed by the surrounding article and by the operations shown in the formula.

Where the article explains it

The rate at which a fluid stream removes heat is Q˙\dot{Q} = m˙\dot{m}\,cpc_p\,Δ\Delta T = ρ\rho\,V˙\dot{V}\,cpc_p\,Δ\Delta T, with mass flow m˙\dot{m} , specific heat capacity cpc_p , and the temperature rise Δ\Delta T across the load.

The passage around this formula

The following is my own worked calculation, using standard property values rather than any cited source. At around 27 °C and atmospheric pressure, air has ρ\rho cpc_p ≈\approx 1.17\ kJ/(m3⋅K)\mathrm{kJ/(m^3{\cdot}K)} ; liquid water has ρ\rho cpc_p ≈\approx 4180\ kJ/(m3⋅K)\mathrm{kJ/(m^3{\cdot}K)} . The ratio is roughly 3,600 to one. Rejecting 100 kW at a 15 K rise therefore requires about 5.7\ m3/s\mathrm{m^3/s} of air — near 12,000 cubic feet per minute, through a single rack aperture — or about 1.6\ L/s\mathrm{L/s} of water, which is a garden hose. There is no engineering cleverness that closes a factor of 3,600; the only levers are a larger Δ\Delta T or a larger duct, and both run out.

Read this part in the article →

Learn the underlying idea

A subscript is a label attached below a symbol. It often selects a time step, component, category, or member of a sequence.

Open the illustrated subscripts: which member of a family? guide →

See this notation across published equations →

Sources cited in the article section

These citations provide research context; check each source for the exact claim it supports.