TDD=100IL∑h=250Ih2 %,\mathrm{TDD} = \frac{100}{I_L}\sqrt{\sum_{h=2}^{50} I_h^2}\ \%,
fraction

What this part means

Divide the expression above the line by the one below it.

Its job in the formula

The expression above the fraction bar is divided by the complete expression below it. The denominator must not be zero.

The passage around this formula

The instrumentation baseline for a new site starts with IEEE 519, the North American reference for harmonic control, which frames the problem around the point of common coupling — the interface between the utility and the customer — and assigns the utility responsibility for background voltage distortion while assigning the customer responsibility for the current distortion its own equipment injects [ 7 ] . The standard’s working measure of current distortion, total demand distortion, is the root-sum-square of harmonic currents up to the fiftieth order expressed as a fraction of the maximum demand current ILI_L rather than of the instantaneous fundamental: TDD=100IL∑h=250Ih2 %\mathrm{TDD} = \frac{100}{I_L}\sqrt{\sum_{h=2}^{50} I_h^2}\ \%. a normalization…